[NMR Pipe Protector Verification Results] Tower Building #T

The water supply piping made of galvanized steel pipes with a statutory useful life of 15 years has been extended for 42 years until it is 57 years old!

This property has been in existence for 37 years, and due to the use of SGP (galvanized steel pipes) for the water supply pipes, there has been an occurrence of red water. Additionally, updating the piping requires a huge cost, and the necessary water outage work during the piping update could not be carried out due to business operations within the building, making it impossible to repair the piping. Therefore, we adopted the "NMR Pipe Protector," which prevents the occurrence of red rust in the pipes by converting it to black rust without allowing red rust to leak out, thus extending the life of the piping. Two months after installation, the complete leaching of red rust stopped, and three months after installation, an analysis of the black rust mass in the piping showed that 63.5% of black rust was confirmed. [Introduction Overview] ■ Before installation: The iron ion concentration in the water inside the pipes was 2.2 mg/l, with a color degree of 50. ■ Effects after installation: - Two months after installation, the complete leaching of red rust stopped. - Three months after installation, an analysis of the black rust mass in the piping confirmed 63.5% black rust. - Even after 20 years, the water supply piping continues to be used without any red rust issues. *For more details, please refer to the PDF document or feel free to contact us.

  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hospital #H

Preventing the leaching of red rust in the hospital's air conditioning chilled and hot water piping and demonstrating rust prevention effectiveness!

At Hospital #H, which was built 48 years ago, the air conditioning chilled and warm water piping using galvanized steel pipes (SGP) has shown significant deterioration due to red rust, leading to leaks. Therefore, we installed the red rust prevention piping extension device "NMR Pipe Protector." Before installation, we sampled the circulating chilled and warm water from the air conditioning system, revealing a total iron concentration of 2.5 mg/l, indicating that red rust corrosion was progressing within the pipes. Four weeks after the installation of our product, a subsequent water sample showed a significant reduction in total iron concentration in the chilled and warm water to 0.4 mg/l. A water sample taken six years after installation showed the total iron concentration further decreased to 0.2 mg/l, completely halting the progression of new red rust within the air conditioning chilled water pipes. The existing red rust had transformed into an insoluble, passive black rust with a volume reduced to one-tenth. [Introduction Overview] ■ Hospital Location: Hamamatsu City, Shizuoka Prefecture ■ Hospital Overview: 41 years old, 2 basement floors and 9 above-ground floors with 606 beds ■ Installation Date: December 2013 *For more details, please refer to the PDF document or feel free to contact us.

  • hos-h1.jpg
  • hos-h2.jpg
  • hos-h3_sb1.jpg
  • hos-h3_sb2.jpg
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hospital #I

Verification of rust reduction in chilled water of air conditioning systems for anti-corrosion effectiveness! Case study on measures to prevent leaks and extend the lifespan of air conditioning piping!

At Hospital #I, due to the significant deterioration of red rust in the air conditioning chilled and hot water piping, which uses galvanized steel pipes (SGP) that are 19 years old, we installed a red rust prevention piping extension device called "NMR Pipe Protector" to prevent leaks. Before the installation of this product, we sampled the circulating air conditioning chilled and hot water, and found that the total iron content in the water was very high at 5.1 mg/l due to red rust, indicating that corrosion from red rust in the piping was quite advanced. Three weeks after the installation, a sample of the air conditioning chilled and hot water showed that the total iron content in the water had decreased to less than 0.03 mg/l, completely halting the progression of new red rust in the air conditioning chilled and hot water. It was demonstrated that the red rust that had been present in the piping had transformed into insoluble black rust, which is 1/10th the volume of the original. If Hospital #I continues to use this product, the air conditioning chilled and hot water piping will no longer require updates in the future, and costs will be reduced to less than 1/10th, extending the lifespan of the building. *For more details, please refer to the PDF document or feel free to contact us.

  • screenshot_02.png
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hospital #NT

A case where the progression of new red rust in the air conditioning chilled and hot water piping completely stopped just 52 days after installation!

The hospital had been built for 27 years at the time, and the air conditioning chilled and warm water piping, which used galvanized steel pipes (SGP), was experiencing significant deterioration due to red rust, raising concerns about leaks. Before the red rust corrosion could progress any further, a red rust prevention piping extension device called "NMR Pipe Protector" was installed. After 52 days of installation, under the same conditions, the water sampled from the air conditioning warm water showed a transparent color, and the water quality test results indicated that the iron ion concentration in the water was 0.27 mg/l, which is below the water quality standard value (1.0 mg/l) set by the Japan Refrigeration and Air Conditioning Industry Association. If this product continues to be installed in the hospital's air conditioning chilled and warm water piping, it has been verified that the red rust deterioration and leaks in the piping will be completely prevented, extending the piping's lifespan to that of the building. [Introduction Overview] ■ Hospital Location: Sendai City, Miyagi Prefecture ■ Hospital Overview: 27 years old, 5 stories, 199 beds ■ Installation Work: December 25 to 28, 2006 *For more details, please refer to the PDF document or feel free to contact us.

  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hospital #A

In one year, a total of four units were installed for the water supply and hot water supply piping, in addition to the air conditioning hot water piping!

At Hospital #A, which was built 31 years ago and uses galvanized steel pipes (SGP) for its air conditioning hot water piping, the deterioration due to red rust has progressed significantly. To prevent future leaks, we installed a red rust prevention pipe extension device called the "NMR Pipe Protector." Before installation, we sampled the circulating air conditioning hot water, and the total iron content in the water was found to be 130 mg/l due to red rust, indicating severe corrosion within the pipes. Two weeks after the installation of our product, the total iron content in the air conditioning hot water was significantly reduced to 4.6 mg/l. Furthermore, four weeks after installation, the total iron content was measured at 2.7 mg/l, a reduction to 1/50 of the initial value. The progression of new red rust within the pipes was completely halted, and the existing red rust had transformed into an insoluble form in water, changing into black rust with a volume reduction to one-tenth. [Introduction Overview] ■ Hospital Location: Sapporo City, Hokkaido ■ Hospital Overview: 31 years old, 1 basement floor and 4 above-ground floors with 554 beds ■ Installation Date: April 2018 *For more details, please refer to the PDF document or feel free to contact us.

  • screenshot_02.png
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hospital #K

The progression of new red rust inside the piping has completely stopped! The durability of the red rust prevention effect has been demonstrated.

At Hospital #K, which was built 30 years ago, deterioration due to red rust in the air conditioning chilled and warm water piping using galvanized steel pipes (SGP) has progressed. To prevent leakage, a red rust prevention piping extension device called "NMR Pipe Protector" was installed. Before installation, a sample of the circulating air conditioning chilled and warm water was taken, revealing that the total iron content in the water was 3.6 mg/l, indicating significant red rust corrosion within the piping. Ten years after installation, effectiveness verification through sampling and analysis by an external organization showed that the iron content remained at a favorable level of 0.2 mg/l, demonstrating the sustainability of the red rust prevention effect provided by the product. 【Introduction Overview】 ■ Hospital Location: Edogawa Ward, Tokyo ■ Hospital Overview: 31 years old, 4 stories, 144 beds ■ Installation Date: December 2020 ■ Installed Piping/Number of Installations ・Secondary side chilled and warm water (supply) main line of air conditioning generator (SGP pipe 150mm)/PT-150DS×1 unit ■ Effect Measurement Method: Effect verification through sampling *For more details, please refer to the PDF document or feel free to contact us.

  • screenshot_02.png
  • screenshot_03.png
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

[NMR Pipe Protector Verification Results] Hotel Serve Shibuya

Completely prevent water leakage damage from air conditioning piping used in hotels!

At Hotel Serve Shibuya, galvanized steel pipes (SGP) are used for the air conditioning chilled and hot water piping, and there was a concern about the deterioration due to red rust and leakage from the joints. As a countermeasure against red rust deterioration and leakage, a red rust prevention pipe longevity device called "NMR Pipe Protector" was installed. Before the installation of the NMR Pipe Protector, water samples were taken from the air conditioning chilled and hot water piping, revealing that the water was tinted light brown, with a total iron content of 5.8 mg/l, indicating significant red rust corrosion within the pipes. Two weeks after the installation of the NMR Pipe Protector, the total iron content in the water within the air conditioning chilled and hot water piping significantly decreased to 0.6 mg/l. In a water sample taken four weeks after the installation, the water was nearly transparent, with the total iron content further reduced to 0.5 mg/l. It was proven that new red rust was completely prevented within the air conditioning chilled and hot water piping, and the existing red rust had transformed into inert black rust. Going forward, if the use of the NMR Pipe Protector continues to prevent external corrosion at Hotel Serve Shibuya, all red rust in the air conditioning chilled and hot water piping will change to black rust, and it has been demonstrated that this piping can be extended to the lifespan of the building. Naturally, leakage has been completely prevented thereafter.

  • hot-s_02.jpg
  • hot-s_g.jpg
  • ホテルサーブ渋谷.jpg
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

Before the pipes start leaking, you can have rust-free pipes! NMR Pipe Protector

Pipes that have been left unattended for over 20 years may have leakage issues!

Preventing piping troubles before they occur. The NMR Pipe Protector, with numerous implementation records both domestically and internationally, suppresses the occurrence of red rust and extends the lifespan of existing piping. It incurs no running costs, prolonging the life of current piping and reducing the risk of leaks. The sooner it is installed, the more effective the results will be felt. It has been featured in various media, including industry publications and TV programs. ◆ Implementation Records (excerpt) [United Kingdom] Buckingham Palace, BBC, Houses of Parliament, Cambridge University Hospital, etc. [Japan] Japanese Red Cross Hospital, Shinjuku Famous Bookstore Building, Teigeki Building, famous hotels and department stores, among many others.

  • NMR2.jpg
  • IPROS49239655761742631634.jpeg
  • Piping Materials

Added to bookmarks

Bookmarks list

Bookmark has been removed

Bookmarks list

You can't add any more bookmarks

By registering as a member, you can increase the number of bookmarks you can save and organize them with labels.

Free membership registration

Water supply and air conditioning pipe leak prevention! Cost 1/10! NMR Pipe Protector

Piping that has been in use for over 25 years poses a risk of leakage!

Pipe deterioration measures are shifting from "replacement" to "extension of life." The NMR Pipe Protector demonstrates a life extension effect greater than that of pipe replacement at one-tenth the cost. It has numerous implementation records both domestically and internationally, converting existing red rust into passive black rust and extending the life of pipes to match the lifespan of the building. ◆ Features and Benefits - Long-term extension of water supply and air conditioning pipes is possible at about one-tenth the cost of pipe replacement work. - Early installation reduces the cleaning costs of drainage pipes. - No water outage work is required during installation. - Numerous verification data: Prevents red rust in galvanized steel pipes with a lifespan of 20 years in buildings that are 60 years old (Teigeki Building, Yaesu Entrance Hall, Shinjuku Famous Bookstore Building, Liberal Democratic Party Hall). ◆ Implementation Records (partial excerpt) [United Kingdom] Buckingham Palace, BBC, Houses of Parliament, Cambridge University Hospital, etc. [Japan] Japanese Red Cross Hospital, famous hotels, department stores, and many others.